Schneider Electric 56170 Residual current protection relay, VigiPacT RH99M, 30mA-30A, 12/24VAC 50/60Hz, 12/48VDC, DIN rail mounting
Code: SCH56170
Unit of measure:
EACH
Description
Earth Leakage Circuit Breaker
Brand Name: Schneider Electric
Voltage: 1000 VAC
Current: 30 A
Mounting Type: Din Rail
Length: 74 mm
Width: 54 mm
Height: 97 mm
Temperature Rating: -35 to 70 deg C
9 Adjustable settings
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
| Relative humidity | 95-95 % at 55-55 °C |
| [Us] rated supply voltage | 12...48 V DC 55...120 % |
| Electromagnetic compatibility | electrostatic discharge immunity test: - 4- conforming to IEC 61000-4-2 |
| Ambient air temperature for operation | -35-70 °C |
| Supplier Code | 56170 |
| Residual earth-leakage time delay adjustment type | adjustable 9 settings 0-4.5 s for 0.03-30 A |
| Ambient air temperature for storage | -55-85 °C |
| Reset | manual reset |
| 9 mm pitches | 6 |
| Earthing system | TT |
| IP degree of protection | IP20 on connection terminals: conforming to EN/IEC 60529 |
| Range | VigiPacT |
| Mounting Type | Din Rail |
| Overvoltage category | IV |
| Power consumption in VA | 4 VA |
| Electrical shock protection class | class II |
| Item Name | Earth Leakage Circuit Breaker |
| Range compatibility | VigiPacT A earth leakage current sensor |
| Minimum load | 10 mA at 12 V |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Tightening torque | fault: 0.6-0.6 N.m bottom |
| Current | 30A |
| Earth-leakage protection class | type A |
| Connections - terminals | sensor: screw terminal cable(s) 0.25-0.5mm² flexible AWG 26...AWG 16 |
| Depth | 74mm |
| Mounting support | DIN rail |
| Type of measurement | earth fault current internal measurement- range: 80...100 % |
| Residual earth-leakage sensitity adjustment type | adjustable 9 settings |
| Voltage | 1000 VAC |
| Height | 81mm |
| Width | 54mm |
| Monitoring | power supply (continuous) |
| Earth leakage current | 0.03-30 A |
| [Ithe] conventional enclosed thermal current | 8 A |
| Temperature Rating | -35 to 70 deg C |
| Wire stripping length | sensor: 5mm for top connection |
| Device short name | RH99M |
| Compatibility code | RH99M |
| Mechanical robustness | vibrations 13.2...100 Hz: 0.7 g |
| Network rated voltage | 1000-1000 V - AC at 400 Hz (maximum) |
| Standards | EN/IEC 60947-2 Annex M |
| Brand Name | Schneider Electric |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Test function | local |
| Length | 74 mm |
| Relay application | protection relay |
| Tamperproof of settings | protected by sealable cover |
| Net weight | 0.3 kg |
| IK degree of protection | IK07 conforming to EN 50102 |
| Type of setting | selector |
| Product or component type | residual current protection relay |
We would love your opinion
Was the information on this page helpful?
Thanks for your feedback!
Can't find what you're looking for?
Request now