Schneider Electric A9D40616 Residual current breaker with overcurrent protection (RCBO), Acti9 iSPN Vigi, 1P + N, 16A, 10mA, A type, 6000A, White
Code: SCHA9D40616
Unit of measure:
EACH
Description
A9 ISPN VIGI RCBO 1PN C 16A 10MA A SLIM
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
| Relative humidity | 95-95 % at 55-55 °C |
| Number of protected poles | 1 |
| Surge current | 3000 A |
| Residual current tripping technology | voltage dependent |
| Ambient air temperature for operation | -25-55 °C |
| Earth-leakage protection | integrated |
| Mounting mode | clip-on |
| Comb busbar and distribution block compatibility | YES |
| Supplier Code | A9D40616 |
| Earth-leakage sensitivity | 10 mA |
| Ambient air temperature for storage | -25-70 °C |
| Network frequency | 50 Hz |
| Neutral position | left |
| 9 mm pitches | 2 |
| [Icw] rated short-time withstand current | Icw: 500 A during 8/20 µs impulse withstand |
| Circuit breaker application | distribution |
| Network type | AC |
| Control type | toggle |
| IP degree of protection | IP20 |
| Range | Acti9 |
| Curve code | C |
| Electrical durability | 10000 cycles |
| Local signalling | ON/OFF indication |
| Tightening torque | 2-2 N.m downstream |
| Earth-leakage protection class | type A |
| Connections - terminals | tunnel type terminal (upstream) 1-16mm² flexible |
| Contact position indicator | yes |
| Suitability for isolation | yes |
| [In] rated current | 16 A at 30 °C |
| Earth-leakage protection time delay | instantaneous |
| Depth | 70mm |
| Colour | White |
| Mounting support | DIN rail |
| Mechanical durability | 20000 cycles |
| Breaking capacity | 6000 A Icn at 230/240 V AC 50 Hz |
| Height | 93mm |
| Limitation class | 3 |
| Poles description | 1P + N |
| Width | 18mm |
| Wire stripping length | 13mm for upstream connection |
| Tropicalisation | 2 |
| Trip unit technology | thermal-magnetic |
| [Ue] rated operational voltage | 230/240 V AC 50 Hz |
| [Ui] rated insulation voltage | 400 V AC 50 Hz |
| Standards | IEC 61009-2-2 |
| Brand Name | Schneider Electric |
| [Uimp] rated impulse withstand voltage | 4 kV |
| Product name | iSPN Vigi |
| Magnetic tripping limit | 5...10 x In |
| Locking options description | ON/OFF locking facilities |
| Net weight | 136 g |
| Product or component type | residual current breaker with overcurrent protection (RCBO) |