Schneider Electric ATS480C14Y Soft starter, Altistart 480, 140A, 208 to 690V AC, control supply 110 to 230V AC
Code: SCHATS480C14Y
Unit of measure:
EACH
Description
SOFT STARTER ATS480 140A 208 TO 690V
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
| Product destination | asynchronous motors |
| With safety function Safe brake management (SBC/SBT) | false |
| Relative humidity | 0-95 % without condensation or dripping water conforming to IEC 60068-2-3 |
| Data format | 8 bits- configurable odd- even or no parity |
| With safety function Safe Speed Monitor (SSM) | false |
| Maximum deflection under vibratory load (during operation) | 1.5mm at 2...13 Hz |
| Ambient air temperature for operation | -15-40 °C (without derating) |
| Connector type | 1 RJ45 |
| Minimum switching current | 100 mA at 12 V DC for relay outputs |
| Analogue output type | current output AQ1: 0...20 mA or 0...10 V- impedance <500 Ohm |
| Ambient air temperature for storage | -25-70 °C |
| Number of addresses | 0-227 for Modbus serial |
| Discrete output type | (DQ2) programmable digital output <= 30 V |
| Apparent power | 0.09 kVA |
| Discrete input number | 4 |
| Protection type | line supply phase loss: motor |
| Motor power kW | 30.0 kW at 230 V in the motor supply line heavy duty |
| Device connection | to the motor delta terminals |
| With safety function Safely Limited Position (SLP) | false |
| Option card | communication module for CANopen Sub-D |
| Pollution degree | level 3 |
| With sft fct Safe Stop 2 (SS2) | false |
| With safety function Safely Limited Speed (SLS) | false |
| Product specific application | process and infrastructures |
| Input compatibility | DI3: discrete input level 1 PLC conforming to IEC 61131-2 |
| Accuracy class | class 10E |
| Discrete input logic | programmable digital input at State 0: < 5 V |
| With safety function Safe torque off (STO) | false |
| Depth | 272.0mm |
| Volume of cooling air | 138.0 m3/h |
| Output current drift | 150-700 % |
| Maximum deflection under vibratory load (during transport) | 1.75mm at 2...9 Hz |
| Width | 200.0mm |
| Operating altitude | > 1000...4000 m with current derating 1 % per 100 m |
| Device short name | ATS480 |
| Maximum acceleration under vibratory load (during storage) | 10 m/s² at 9...200 Hz |
| Power loss static current independent | 25.0 W |
| Method of access | slave Modbus serial |
| Output compatibility | open collector level 1 PLC conforming to IEC 65A-68 |
| Relay output number | 3 |
| Analogue output number | 1 |
| [Ui] rated insulation voltage | 690 V |
| Transmission frame | RTU |
| Analogue input number | 1 |
| Supply frequency | 50...60 Hz - 20...20 % |
| Environmental class (during operation) | class 3S2 according to IEC 60721-3-3 |
| Torque control | true |
| Discrete input type | (DI4) programmable as logic input- 3500 Ohm |
| Net weight | 12.4 kg |
| Transmission rate | 1200...256000 bit/s |
| [Us] rated supply voltage | 208...690 V - 15...10 % |
| With safety function Safe Stop 1 (SS1) | false |
| Operating position | vertical +/- 10 degree |
| Electromagnetic compatibility | conducted and radiated emissions with bypass level B conforming to IEC 60947-4-2 |
| With safety function Safe Direction (SDI) | false |
| Noise level | 50.0 dB |
| Supplier Code | ATS480C14Y |
| Network frequency | 50/60 Hz |
| Type of polarization | no impedance for Modbus serial |
| Communication data link | serial |
| With safety function Safe Operating Stop (SOS) | false |
| Network number of phases | 3 phases |
| With safety function Safe Position (SP) | false |
| Function available | single direction |
| Analogue input type | PTC2 PTC/Pt 100 temperature probe |
| Maximum acceleration under shock load (during transport) | 100 m/s² at 11 ms |
| Communication port protocol | Modbus serial |
| IP degree of protection | IP00 |
| Range | Altivar Soft Starter ATS480 |
| Display screen available | true |
| [Ie] rated operational current | normal duty: 140.0 A (at <40 °C) |
| Maximum acceleration under vibratory load (during transport) | 10 m/s² at 9...200 Hz |
| Power loss per device current dependent | 366.0 W |
| Maximum permanent current | 110.0 A at 40 °C for heavy duty |
| Suitable for mounting onto standard rails | false |
| Maximum switching current | |
| Integrated motor overload protection | true |
| Height | 340.0mm |
| Relay output type | relay outputs R1A 1 NO |
| Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 13...200 Hz |
| [Uc] control circuit voltage | 110...230 V AC 50/60 Hz - 15...10 % |
| Rated current pwr loss specification | 140.0 A |
| Discrete output number | 2 |
| Marking | UKCA |
| Maximum deflection under vibratory load (during storage) | 1.75mm at 2...9 Hz |
| Standards | IEC 60664-1 |
| Product certifications | RCM |
| With safety function Safe programmable logic | false |
| Brand Name | Schneider Electric |
| Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Motor power hp | 125.0 hp at 575 V normal duty |
| Utilisation category | AC-53A |
| Physical interface | 2-wire RS 485 |
| Maximum acceleration under shock load (during storage) | 100 m/s² at 11 ms |
| Product or component type | soft starter |