Schneider Electric GV2P10 Motor circuit breaker, TeSys GV2, TeSys Deca, 3P, 4 to 6.3A, thermal magnetic, screw clamp terminals, rotary handle, Dark Grey
Code: SCHGV2P10
Unit of measure:
EACH
Description
Motor Protection Circuit Breaker
Brand Name: Schneider
Type: Thermal Magnetic
Range: TeSys GV2
Voltage: 690 VAC
Current Type: AC
Current: 4 - 6.3 A
Power Rating: 4 kW
Number of Poles: 3
Break Strength: 6 kA
Frequency Rating: 50/60 Hz
Connection Type: Screw Clamp
Rotary Handle
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
| Maximum operating rate | 25 cyc/h |
| Ambient air temperature for operation | -20-60 °C |
| [Ith] conventional free air thermal current | 6.3 A conforming to IEC 60947-4-1 |
| Supplier Code | GV2P10 |
| Connection Type | Screw Terminal |
| Ambient air temperature for storage | -40-80 °C |
| Network frequency | 50/60 Hz conforming to IEC 60947-4-1 |
| Network type | AC |
| Fixing mode | panel: screwed (with 2 x M4 screws) |
| Motor power kW | 3-3 kW at 500 V AC 50/60 Hz |
| Magnetic tripping current | 91-91 A |
| Control type | rotary handle |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Range | Galaxy VL |
| Electrical durability | 100000 cycles for AC-3e at 415 V In |
| Item Name | Circuit Breaker |
| Mounting position | vertical |
| Tightening torque | 1.7 N.m - on screw clamp terminal |
| Thermal protection adjustment range | 4-6.3 A conforming to IEC 60947-4-1 |
| Current | 6.3A |
| [Ics] rated service short-circuit breaking capacity | 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
| Standard | CCC, CSA, UL Listed |
| Suitability for isolation | yes conforming to IEC 60947-1 |
| [In] rated current | 6.3 A |
| Depth | 97mm |
| Colour | Dark Grey |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Mechanical durability | 100000 cycles |
| Climatic withstand | conforming to IACS E10 |
| Voltage | 690V |
| Direct connector | without |
| Breaking capacity | 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Height | 89mm |
| Poles description | 3P |
| Width | 45mm |
| Operating altitude | 2000 m |
| Device short name | GV2P |
| Phase failure sensitivity | yes conforming to IEC 60947-4-1 |
| Compatibility code | GV2P |
| Trip unit technology | thermal-magnetic |
| Mechanical robustness | vibrations: 5 Gn- 5...150 Hz |
| Device application | motor protection |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Standards | IEC/EN 60335-1:Clause 30.2 |
| Product certifications | BV |
| Brand Name | Schneider Electric |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Power dissipation per pole | 2.5 W |
| Product name | TeSys GV2 |
| Utilisation category | AC-3 conforming to IEC 60947-4-1 |
| Rated duty | continuous conforming to IEC 60947-4-1 |
| IK degree of protection | IK04 |
| Product or component type | motor circuit breaker |
We would love your opinion
Was the information on this page helpful?
Thanks for your feedback!
Can't find what you're looking for?
Request now
We can source just about anything, submit a request and we'll get back to you soon.