Description
Schneider LC1D80008U7 Contactor, TeSys Deca, 4P(2NO+2NC), AC-1, <=440V, 125A, 240V AC 50/60Hz coil
TeSys Deca contactor, 4 poles(4NO) for category AC-1 applications up to 200A @440V. It provides with 240V 50/60 Hz coil, with no auxiliary contacts, power and control connections by lugs and bars. It procures high reliability and durability with 8 Mcycles mechanical durability and 0.8 Mcycles electrical durability. It provides IP20 protection on front face conforming to IEC 60529. It can cover -40°C to 60°C operation temperature and without derating under 3000m altitude. Designed for demanding applications with maximum operating rates up to 2400 cycles per hour under maximum 60°C. The dimension is 158mm x 155mm x 115mm (H x W x D), mounting on rail or plate. Multi standards certified(CCC,DNV,GL,CSA,GOST,BV,UL,LROS,RINA,UKCA) and Green Premium compliant (RoHs/Reach).
Features:
• Designed to meet needs of demanding applications
• Digital customer experience for technical documents
• New modern look & feel of all machines
• Easier to install and operate with multi-standard screws
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
| Contactor application | resistive load |
| Maximum operating rate | 2400 cyc/h at 60 °C |
| Mount | Rail |
| Irms rated making capacity | 1260 A at 440 V for power circuit conforming to IEC 60947 |
| [Ith] conventional free air thermal current | 200 A (at 60 °C) for power circuit |
| Supplier Code | LC1D1150046U7 |
| Breaking Capacity | 1100 A |
| [Icw] rated short-time withstand current | 1100 A 40 °C - 1 s for power circuit |
| Inrush power in VA | 280-350 VA 50 Hz cos phi 0.8 (at 20 °C) |
| Hold-in power consumption in VA | 2-18 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Safety reliability level | B10d = 10000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Range | TeSys |
| Flame retardance | V1 conforming to UL 94 |
| Weight | 2.86 kg |
| Overvoltage category | III |
| Electrical durability | 0.8 Mcycles 200 A AC-1 at Ue <= 440 V |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Protective cover | with |
| Pollution degree | 3 |
| Tightening torque | power circuit: 12 N.m - on lugs-ring terminals hexagonal screw head 13mm M8 |
| Average impedance | 0.6 mOhm - Ith 200 A 50 Hz for power circuit |
| [Ie] rated operational current | 200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit |
| Connections - terminals | power circuit: lugs-ring terminals - external diameter: 25mm |
| Control circuit type | AC at 50/60 Hz |
| Associated fuse rating | 200 A gG at <= 690 V coordination type 2 for power circuit |
| Depth | 115mm |
| Mounting support | rail |
| Pole contact composition | 4 NO |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Voltage | <= 460 V |
| Mechanical durability | 8 Mcycles |
| Permissible ambient air temperature around the device | 60-70 °C with derating |
| Climatic withstand | conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Coil technology | built-in bidirectional peak limiting diode suppressor |
| Height | 158mm |
| Poles description | 4P |
| Width | 155mm |
| Operating altitude | 0...3000 m |
| Operating time | 20...50 ms closing |
| Device short name | LC1D |
| [Uc] control circuit voltage | 240 V AC 50/60 Hz |
| Compatibility code | LC1D |
| Mechanical robustness | shocks contactor closed (15 Gn for 11 ms) |
| [Ue] rated operational voltage | power circuit: <= 460 V DC |
| Pole Configuration | 4 Pole |
| [Ui] rated insulation voltage | power circuit: 1000 V conforming to IEC 60947-4-1 |
| Contact compatibility | M14 |
| Standards | EN 60947-4-1 |
| Control circuit voltage limits | 0.8...1.15 Uc (-40-55 °C):operational AC 50/60 Hz |
| Product certifications | CSA |
| Brand Name | Schneider Electric |
| Heat dissipation | 3-8 W at 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Power dissipation per pole | 24 W AC-1 |
| IP Rating | IP20 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| Utilisation category | AC-3e |
| Net weight | 2.86 kg |
| Product or component type | contactor |
We would love your opinion
Was the information on this page helpful?
Thanks for your feedback!