Schneider Electric LC1D80AB7 Contactor, TeSys Deca, 3P(3 NO), AC-3/AC-3e, <=440V, 66A, 24V AC 50/60Hz coil, EverLink+springs
TeSys D contactor, 3 poles (3NO), for motor control applications up to 66A/440V AC-3 (37kW@400V). It provides a 24V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by EverLink BTR screw connectors, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (55mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Mount | Plate |
| Control circuit type | AC at 50/60 Hz standard |
| Depth | 120 mm |
| Minimum switching current | 5 mA for signalling circuit |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Pole contact composition | 3 NO |
| Signalling circuit frequency | 25...400 Hz |
| Voltage | 300 V |
| Supplier Code | LC1D80AB7 |
| Mechanical durability | 6 Mcycles |
| Coil technology | without built-in suppressor module |
| Height | 122mm |
| Minimum switching voltage | 17 V for signalling circuit |
| Poles description | 3P |
| Width | 55mm |
| Breaking Capacity | 1000 A |
| Operating altitude | 0...3000 m |
| [Uc] control circuit voltage | 24 V AC 50/60 Hz |
| Device short name | LC1D |
| Compatibility code | LC1D |
| Pole Configuration | 3 Pole |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Range | TeSys D |
| Contact compatibility | M2 |
| Flame retardance | V1 conforming to UL 94 |
| Weight | 0.86 kg |
| Overvoltage category | III |
| Brand Name | Schneider Electric |
| Heat dissipation | 4-5 W at 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| IP Rating | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Protective cover | with |
| Rated breaking capacity | 1000 A at 440 V for power circuit conforming to IEC 60947 |
| Pollution degree | 3 |
| Average impedance | 1.5 mOhm - Ith 80 A 50 Hz for power circuit |
| Net weight | 0.86 kg |
| Auxiliary contact composition | 1 NO + 1 NC |
| Product or component type | contactor |
We would love your opinion