Schneider Electric Current transformer TI current transformer tropicalised DIN mount 250 5 for bars 10x40 20x32 25x25
Code: SCHMETSECT5MC025
Unit of measure:
EACH
Description
Schneider Electric Current transformer TI current transformer tropicalised DIN mount 250 5 for bars 10x40 20x32 25x25
This current transformer, tropicalised for busbar and cable, has a line rated current of 250 A and a secondary current rating of 5 A. This current transformer do have a 41 mm x 41 mm opening. Compatible with a triple output for bar: 40.5 mm x 10.5 mm or 32.5 mm x 20.5 mm or 25.5 mm x 25.5 mm. Burden and accuracy class as follows: class 0.5 maximum power: 3 VA, class 1 maximum power: 5 VA.
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
| Relative humidity | 0-95 % |
| Maximum safety factor | 5 |
| Standard | IEC 61869-2 |
| [In] rated current | 250 A |
| Depth | 65mm |
| Ambient air temperature for operation | -25-60 °C |
| [Ith] conventional free air thermal current | 15 kA |
| Supplier Code | METSECT5MC025 |
| Height | 41mm |
| Width | 41mm |
| Diameter | 32mm |
| Electrical insulation class | class B |
| Compatibility code | MC |
| [Ue] rated operational voltage | < 720 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 3 kV |
| Range | PowerLogic |
| Sealing | without |
| Brand Name | Schneider Electric |
| [Uimp] rated impulse withstand voltage | 3 kV |
| Cable outer diameter | 32 mm |
| Dynamic withstand current | 2.5 Ith |
| IP Rating | IP20 |
| Current transformer type | tropicalised for busbar and cable |
| Product name | CT |
| Secondary current | 5 A |
| Net weight | 0.375 kg |
| Current transformer ratio | 250/5 |
| Product or component type | current transformer |