Schneider Electric RMNF22TB30 3-phase control relay, Harmony Control Relays, 8A, 2CO, overfrequency and underfrequency, 208…480V AC
Code: SCHRMNF22TB30
Unit of measure:
EACH
Description
NFC CONTROL RELAY 3-PHASES
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
| Relative humidity | 93-97 % at 25-55 °C conforming to IEC 60068-2-30 |
| [Us] rated supply voltage | 120...277 V AC 50/60 Hz- non self-powered |
| Dielectric test voltage | 2.5 kV- 1 min AC 50 Hz conforming to IEC 60255-27 |
| Time delay type | adjustable 0.1 s...1 min Tt- time delay upon fault |
| Maximum switching voltage | 250 V AC |
| Electromagnetic compatibility | voltage dips and interruptions immunity test - test level: 40 % (10/12 cycles) conforming to IEC 61000-4-11 |
| Ambient air temperature for operation | -20-60 °C |
| Minimum switching current | 100 mA at 6 V |
| [Ith] conventional free air thermal current | 8 A |
| Directives | 2014/35/EU - low voltage directive |
| Supplier Code | RMNF22TB30 |
| Ambient air temperature for storage | -40-70 °C |
| Supply voltage limits | 96-332.4 V AC line to neutral |
| Maximum operating frequency | 13.56 MHz |
| Hysteresis | 3-3 % of fixed for phase failure detection |
| Vibration resistance | 0.035mm (f= 10-58.1 Hz) in operation conforming to IEC 60068-2-6 |
| Repeat accuracy | +/- 3 % for time delay |
| Network number of phases | 3 phases |
| Shock resistance | 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27 |
| Contacts type and composition | 2 C/O |
| Insulation resistance | > 100 MOhm at 500 V DC conforming to IEC 60255-27 |
| Control type | without test button |
| IP degree of protection | IP40 (housing) conforming to IEC 60529 |
| Range | Harmony Control Relays |
| Overvoltage category | III conforming to UL 508 |
| Measurement range | 208...480 V AC |
| Power consumption in VA | 4-4 VA at 480 V AC 60 Hz |
| Electrical durability | 100000 cycles |
| Response time | <= 300 ms |
| Local signalling | LED UV: (steady)- red for alarm undervoltage failure triggered |
| Setting accuracy of the switching threshold | +/- (1.5 % + 1 V) |
| Mounting position | any position |
| Pollution degree | 3 conforming to UL 508 |
| Tightening torque | 5.3-8.8 lbf.in conforming to IEC 60947-1 |
| Relay type | control relay |
| Connections - terminals | screw terminals- 1 x 0.5...1 x 2.5mm² (AWG 20...AWG 14) flexible with cable end |
| Output contacts | 2 C/O |
| Alarm threshold | 5...150 V adjustable asymmetry |
| Maximum measuring cycle | 150 ms measurement cycle as true rms value |
| Setting accuracy of time delay | +/- 300 ms for 0...10 s time delay range |
| Software designation | Ecostruxure Industrial Device (downloadable from Google Play store or Apple Store) |
| [In] rated current | 8 A |
| Depth | 99mm |
| Mounting support | 35mm DIN rail conforming to IEC 60715 |
| Mechanical durability | 10000000 cycles |
| Relay monitored parameters | overfrequency and underfrequency |
| Maximum switching current | 8 A AC |
| Height | 90mm |
| Switching capacity in VA | 2000 VA |
| Housing material | self-extinguishing plastic |
| Width | 22.5mm |
| Measurement error | < 0.05 %/°C with temperature variation |
| Operating system | iOSversion >= V14.5 |
| [Uc] control circuit voltage | 120...277 V |
| Product compatibility | NFC enabled mobile device |
| Nominal power | 0.0002 mW |
| Contacts material | cadmium free |
| Relay name | RMNF22 |
| [Ui] rated insulation voltage | 400 V |
| Standards | IEC 60255-1 |
| Product certifications | CCC |
| Threshold adjustment voltage | 2...20 % of Un selected |
| Brand Name | Schneider Electric |
| On-load factor | 100 % |
| Supply frequency | 50...60 Hz +/- 10 % |
| [Uimp] rated impulse withstand voltage | 4 kV during 1.2/50 µs |
| Immunity to microbreaks | 10 ms |
| Reset time | 1500 ms at maximum voltage |
| Utilisation category | AC-1 conforming to IEC 60947-4-1 |
| Net weight | 0.125 kg |
| Adjustment of asymmetry threshold | 2...20 % of Un selected |
| Product or component type | NFC control relay |
| Run-up delay at power-up | 650 ms |