Schneider Electric XPSUAF13AP safety module, Harmony XPSU, Cat 4, potential free 2 NC, NO NC, 2 PNP, 24V AC or DC, screw
Code: SCHXPSUAF13AP
Unit of measure:
EACH
Description
SAFETY MODULE UAF CAT.4 24V SCREW
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
| Relative humidity | 5-95 % non-condensing |
| [Us] rated supply voltage | 24 V DC - 20...20 % |
| Safety reliability data | HFT = 1 conforming to IEC 62061 |
| Input compatibility | antivalent pair conforming to ISO 14119 |
| Associated fuse rating | 10 A gG for NO relay output circuit conforming to IEC 60947-1 |
| Safety module application | for emergency stop- guard and light curtain monitoring |
| Safety level | can reach SIL 3 conforming to IEC 61508 |
| Depth | 120mm |
| Input/output type | semiconductor pulsed diagnostic output 24 V DC- 20 mA Z1- not safety-related |
| Maximum line resistance | 500 Ohm |
| Input protection type | internal- electronic |
| Mounting support | 35mm symmetrical DIN rail |
| Synchronisation time between inputs | 2 s |
| Type of start | automatic/manual/monitored |
| [Ith] conventional free air thermal current | 8 A |
| Number of outputs | 3 on/off configurable pulsed output |
| Function of module | light curtain monitoring |
| Supplier Code | XPSUAF13AP |
| Ambient air temperature for storage | -25-85 °C |
| Safety module name | XPSUAF |
| Height | 100mm |
| Number of inputs | 2 safety input 24 V DC 5 |
| Width | 22.5mm |
| Power consumption in W | 2.0 W 24 V DC |
| Minimum output voltage | 15 V for relay output |
| Minimum output current | 10 mA for relay output |
| IP degree of protection | IP54 (mounting area) conforming to IEC 60529 |
| [Ui] rated insulation voltage | 250 V (pollution degree 2) conforming to IEC 60947-1 |
| Range | Harmony Safety Automation |
| Standards | ISO 13849-1 functional safety standard |
| Power consumption in VA | 5.0 VA 24 V AC 50/60 Hz |
| Product certifications | cULus |
| Brand Name | Schneider Electric |
| [Uimp] rated impulse withstand voltage | 4 kV overvoltage category II conforming to IEC 60947-1 |
| Electrical circuit type | PNP pair |
| Local signalling | LED (red) for error |
| Net weight | 0.200 kg |
| Auxiliary contact composition | 3 NO |
| [Ie] rated operational current | 3 A AC-15 for normally open relay contact |
| Product or component type | safety module |
| Maximum response time on input open | 20 ms |
| Connections - terminals | removable screw terminal block- 2 x 0.25...1mm² flexible with ferrule without cable end- with bezel |
We would love your opinion
Was the information on this page helpful?
Thanks for your feedback!
Can't find what you're looking for?
Request now
We can source just about anything, submit a request and we'll get back to you soon.