Description
Schneider Electric EasyPact CVS circuit breaker EasyPact CVS160F, 36 kA at 415 VAC, 125 A rating thermal magnetic TM-D trip unit, 3P 3d
EasyPact CVS160F is a 3 poles 3d fixed circuit breaker with a high level of performance and cost-saving functionality. It is an optimal choice for small and medium-sized buildings protection applications. The breaking capacity (Icu) is 36kA rms at 415VAC 50/60Hz. The operational voltage is 440VAC 50/60Hz. This product embeds a 125A rating thermal-magnetic trip unit (TMD). TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection. This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. EasyPact CVS160F is compliant with international standards (IEC 60947, CCC, EAC). It can be installed in class II insulation switchboards as it is a class II front face device (IEC 60664-1).
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Poles | 3 Pole |
Mount | Backplate |
Long time pick-up adjustment type Ir | adjustable |
Downside connection | front |
Ambient air temperature for operation | -25-70 °C |
Instantaneous pick-up adjustment type Ii | fixed |
[Ics] rated service breaking capacity | 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 |
Earth-leakage protection | without |
Mounting mode | fixed |
Breaking capacity code | F |
Supplier Code | LV516332 |
Connection Type | Screw Terminal |
Ambient air temperature for storage | -50-85 °C |
Trip unit name | TM-D |
Network frequency | 50/60 Hz |
Breaking Capacity | 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 |
Protection type | short-circuit protection (magnetic) |
Network type | AC |
Control type | toggle |
IP degree of protection | IP40 |
Range | EasyPact |
Weight | 1.8kg |
Long time pick-up adjustment range | 0.7...1 x In |
Electrical shock protection class | class II |
Electrical durability | 12000 cycles 415 V In conforming to IEC 60947-2 |
Item Name | Circuit Breaker |
Pollution degree | 3 conforming to IEC 60664-1 |
Thermal protection adjustment range | 87.5-125 A |
Current | 100A |
Connections - terminals | screw connection |
Trip unit rating | 125-125 A at 40 °C |
Contact position indicator | yes |
Standard | IEC 60947-2 |
[In] rated current | 125 A at 40 °C |
Connection pitch | 35mm |
Depth | 86mm |
Mounting support | backplate |
Instantaneous pick-up adjustment range | 1250 A |
Mechanical durability | 25000 cycles |
Height | 161mm |
Poles description | 3P |
Width | 105mm |
Protected poles description | 3D |
Device short name | CVS160F |
Compatibility code | CVS160 |
Trip unit technology | thermal-magnetic |
Device application | distribution |
Standards | IEC 60947-2 |
Product certifications | IEC |
Brand Name | Schneider Electric |
[Uimp] rated impulse withstand voltage | 8 kV conforming to EN/IEC 60947-2 |
Upside connection | front |
Product name | EasyPact CVS |
IP Rating | IP40 |
Utilisation category | category A |
Frequency | 50 - 60Hz |
Net weight | 1.5 kg |
Long time delay adjustment type | fixed |
Product or component type | circuit breaker |
We would love your opinion
Was the information on this page helpful?
Thanks for your feedback!
We can source just about anything, submit a request and we'll get back to you soon.