Schneider Electric C25F3TM200 Circuit breaker, ComPacT NSX250F, 36kA/415VAC, 3 poles, TMD trip unit 200A
Code: SCHC25F3TM200
Unit of measure:
EACH
Description
NSX250F 36KA AC 3P3D 200A TMD
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Relative humidity | 0-95 % |
Long time pick-up adjustment type Ir | adjustable |
Downside connection | front |
Ambient air temperature for operation | -25-70 °C |
Instantaneous pick-up adjustment type Ii | adjustable |
[Ics] rated service breaking capacity | 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 |
Earth-leakage protection | without |
Mounting mode | fixed |
Breaking capacity code | F 36 kA 415 V AC |
Supplier Code | C25F3TM200 |
Ambient air temperature for storage | -50-85 °C |
Trip unit name | TM-D |
Network frequency | 50/60 Hz |
Trip unit protection functions | LI |
Protection type | L : for overload protection (thermal) |
Network type | AC |
Control type | toggle |
IP degree of protection | IP40 conforming to IEC 60529 |
Range | ComPacT new generation |
Overvoltage category | class II |
Long time pick-up adjustment range | 0.7...1 x In |
Electrical shock protection class | class II |
Electrical durability | 10000 cycles at 690 V In/2 |
Mounting position | flat on the back |
Pollution degree | 3 conforming to IEC 60664-1 |
Trip unit rating | 200-200 A at 40 °C |
Suitability for isolation | yes conforming to EN/IEC 60947-2 |
[In] rated current | 200 A at 40 °C |
Depth | 86mm |
Connection pitch | 35mm |
Mounting support | backplate |
Instantaneous pick-up adjustment range | 5...10 x In |
Mechanical durability | 20000 cycles |
Breaking capacity | 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
Height | 161mm |
Poles description | 3P |
Width | 105mm |
Operating altitude | 2000 m...5000 m with derating |
Protected poles description | 3D |
Device short name | NSX250F |
Compatibility code | NSX250 |
Trip unit technology | thermal-magnetic |
Device application | distribution |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz |
Standards | EN/IEC 60947-2 |
Brand Name | Schneider Electric |
[tr] long-time delay adjustment range | 15-15 s at 6 x Ir |
[Uimp] rated impulse withstand voltage | 8 kV |
Upside connection | front |
Power dissipation per pole | 15.4 W |
Product name | ComPacT NSX new generation |
Utilisation category | category A |
Net weight | 2.4 kg |
Long time delay adjustment type | fixed |
IK degree of protection | IK07 conforming to IEC 62262 |
Number of slots | 5 slot(s) |
Product or component type | circuit breaker |