Schneider Electric GV2ME203 Motor circuit breaker,TeSys Deca frame 2,3P,13-18A,thermal magnetic,push button,spring terminals, Dark Grey
Code: SCHGV2ME203
Unit of measure:
EACH
Description
SPRING TERM. MCB
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Maximum operating rate | 25 cyc/h |
Ambient air temperature for operation | -20-60 °C |
[Ith] conventional free air thermal current | 18 A conforming to IEC 60947-4-1 |
Supplier Code | GV2ME203 |
Ambient air temperature for storage | -40-80 °C |
Network frequency | 50/60 Hz conforming to IEC 60947-4-1 |
Network type | AC |
Fixing mode | panel: screwed (with adaptor plate) |
Motor power kW | 9-9 kW at 500 V AC 50/60 Hz |
Magnetic tripping current | 341-341 A |
Control type | push-button |
IP degree of protection | IP20 conforming to IEC 60529 |
Range | TeSys Deca |
Electrical durability | 100000 cycles for AC-3e at 415 V In |
Mounting position | vertical |
Thermal protection adjustment range | 13-18 A conforming to IEC 60947-4-1 |
[Ics] rated service short-circuit breaking capacity | 50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Suitability for isolation | yes conforming to IEC 60947-1 |
[In] rated current | 18 A |
Depth | 78.5mm |
Colour | Dark Grey |
Fire resistance | 960 °C conforming to IEC 60695-2-11 |
Mechanical durability | 100000 cycles |
Climatic withstand | conforming to IACS E10 |
Direct connector | without |
Breaking capacity | 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
Height | 101mm |
Poles description | 3P |
Width | 45mm |
Operating altitude | 2000 m |
Device short name | GV2ME |
Phase failure sensitivity | yes conforming to IEC 60947-4-1 |
Compatibility code | GV2ME |
Trip unit technology | thermal-magnetic |
Mechanical robustness | vibrations: 5 Gn- 5...150 Hz |
Device application | motor protection |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
Standards | IEC/EN 60335-2-40:Annex JJ |
Product certifications | ATEX |
Brand Name | Schneider Electric |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
Power dissipation per pole | 2.5 W |
Product name | TeSys GV2 |
Utilisation category | AC-3 conforming to IEC 60947-4-1 |
Rated duty | continuous conforming to IEC 60947-4-1 |
Net weight | 0.28 kg |
IK degree of protection | IK04 |
Product or component type | motor circuit breaker |