Schneider Electric GV3P65 Motor circuit breaker,TeSys Deca frame 3,3P,48-65A,thermal magnetic,EverLink terminals, Dark Grey
Code: SCHGV3P65
Unit of measure:
EACH
Description
Motor Protection Circuit Breaker
Brand Name: Schneider
Type: Thermal Magnetic
Range: TeSys GV3
Voltage: 690 VAC
Current Type: AC
Current: 48 - 65 A
Power Rating: 55 kW
Number of Poles: 3
Break Strength: 6 kA
Frequency Rating: 50/60 Hz
Connection Type: Screw Clamp
Rotary Handle
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Power Rating | 55 kW |
Maximum operating rate | 25 cyc/h |
Ambient air temperature for operation | -20-60 °C |
Current Type | AC |
[Ith] conventional free air thermal current | 65 A conforming to IEC 60947-4-1 |
Supplier Code | GV3P65 |
Connection Type | Screw Clamp |
Ambient air temperature for storage | -40-80 °C |
Network frequency | 50/60 Hz conforming to IEC 60947-4-1 |
Network type | AC |
Break Strength | 6 kA |
Fixing mode | panel: screwed (with 3 x M4 screws) |
Motor power kW | 45-45 kW at 500 V AC 50/60 Hz |
Magnetic tripping current | 910-910 A |
Control type | rotary handle |
IP degree of protection | IP20 conforming to IEC 60529 |
Range | TeSys Deca |
Frequency Rating | 50/60 Hz |
Electrical durability | 50000 cycles for AC-3 at 415 V In |
Item Name | Motor Protection Circuit Breaker |
Mounting position | vertical |
Tightening torque | 5 N.m - on screw clamp terminal |
Thermal protection adjustment range | 48-65 A conforming to IEC 60947-4-1 |
Current | 48 - 65A |
[Ics] rated service short-circuit breaking capacity | 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Standard | CCC, CSA, UL Listed |
Suitability for isolation | yes conforming to IEC 60947-1 |
[In] rated current | 65 A |
Depth | 136mm |
Colour | Dark Grey |
Fire resistance | 960 °C conforming to IEC 60695-2-11 |
Mechanical durability | 50000 cycles |
Climatic withstand | conforming to IACS E10 |
Voltage | 690 VAC |
Direct connector | without |
Breaking capacity | 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Height | 132mm |
Poles description | 3P |
Width | 55mm |
Operating altitude | 3000 m |
Device short name | GV3P |
Phase failure sensitivity | yes conforming to IEC 60947-4-1 |
Compatibility code | GV3P |
Trip unit technology | thermal-magnetic |
Mechanical robustness | vibrations: 4 Gn- 5...300 Hz |
Device application | motor protection |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
Standards | IEC/EN 60335-1:Clause 30.2 |
Product certifications | UKCA |
Brand Name | Schneider Electric |
EAN/UPC | 3389119405416 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
Type | Thermal Magnetic |
Power dissipation per pole | 8 W |
Product name | TeSys GV3 |
Utilisation category | AC-3 conforming to IEC 60947-4-1 |
Rated duty | continuous conforming to IEC 60947-4-1 |
Net weight | 0.96 kg |
Number of Poles | 3 |
IK degree of protection | IK09 enclosure |
Product or component type | motor circuit breaker |
We would love your opinion
Was the information on this page helpful?
Thanks for your feedback!
Can't find what you're looking for?
Request now
We can source just about anything, submit a request and we'll get back to you soon.