Schneider A9A26946 Acti9 Series Shunt Trip Release with OC Contact, iMX+OF, Voltage Release, 100-415Vac - 110-130Vdc
This Acti 9 MX+OF electrical tripping auxiliary for is a shunt trip release. It is dedicated to Acti9 iC60, iID, iC40, iC40 XA, iCV40, iID40, iCV40 XA, iDPN Vigi, iSW-NA, iKQE, iC60 RCBO. This device includes an open/close contact OF to indicated the position of the associated device. Emergency stoppage by normally open pushbutton. The product trips the associated device when it is powered on by emergency pushbutton. The width in 9mm pitches is 2. The Ue rated operational voltage is 100VAC to 415VAC or 110VDC to 130VDC. The operating frequency is 50Hz or 60Hz. The Ie rated operational current is 6A under 24VDC, 2A under 48VDC, 1.5A under 60VDC, 1A under 130VDC. The Ie rated operational current is 6A under 24VAC to 240VAC, 3A under 415VAC. There is a mechanical state indicator light, red on the front face. The operating temperature is -25°C to + 50°C. The storage temperature is -40°C to + 85°C. This product complies with IEC/EN 60947-5-1 standard and EN 62019-2 standard only for C120.