Schneider Electric XALK188 Emergency Stop, 40mm, M/R, Key Red, 1N/C
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Product destination | for XB5 Ø 22mm control and signalling units |
Positive opening | with conforming to IEC 60947-5-1 appendix K |
Shape of screw head | cross compatible with Philips no 1 screwdriver |
Ambient air temperature for operation | -40-70 °C |
Supplier ref | XALK188 |
[Ith] conventional free air thermal current | 10 A conforming to IEC 60947-5-1 |
Supplier Code | XALK188 |
Mechanical durability | 300000 cycles |
Key number | 455 |
Colour of base of enclosure | light grey (RAL 7035) |
Operators description | red unmarked 1 NC |
Ambient air temperature for storage | -40-70 °C |
Control station composition | 1 mushroom head Ø 40mm push-button- red 1 NC unmarked marking |
Operator profile | 1 mushroom head push-button |
Reset | key release |
Vibration resistance | 5 gn (f= 12-500 Hz) conforming to IEC 60068-2-6 |
NEMA degree of protection | NEMA 13 |
Operating travel | 4.3mm (total travel) |
Device short name | XALK |
Control station application | emergency switching off function |
Compatibility code | XALK |
Shock resistance | 30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27 |
Contacts material | silver alloy (Ag/Ni) |
Material | polycarbonate |
[Ui] rated insulation voltage | 600 V (pollution degree 3) conforming to IEC 60947-1 |
IP degree of protection | IP66 conforming to IEC 60529 |
Range | Harmony XALK |
Standards | IEC 60947-5-4 |
Overvoltage category | class II conforming to IEC 60536 |
Colour of cover | yellow (RAL 1021) |
Short-circuit protection | 10 A cartridge fuse type gG conforming to IEC 60947-5-1 |
Brand Name | Schneider Electric |
Electrical durability | 1000000 cycles- DC-13- 0.5 A at 24 V- operating rate <3600 cyc/h- load factor: 0.5 conforming to IEC 60947-5-1 appendix C |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-1 |
Resistance to high pressure washer | 7000000 Pa at 55 °C- distance : 0.1 m |
Protective treatment | TH |
Operating force | 44 N NC + NO changing electrical state |
Tightening torque | 0.8-1.2 N.m conforming to IEC 60947-1 |
Net weight | 0.188 kg |
Contact operation | slow-break |
Cable entry | 2 knock-outs for Pg 13 cable gland and ISO M20 0-12mm |
IK degree of protection | IK03 conforming to IEC 62262 |
Electrical reliability | λ < 10exp(-8) at 17 V- 5 mA conforming to IEC 60947-5-4 |
[Ie] rated operational current | 0.27 A at 250 V- DC-13- Q600 conforming to IEC 60947-5-1 |
Product or component type | complete control station |
Connections - terminals | screw clamp terminals- >= 1 x 0.22mm² without cable end conforming to IEC 60947-1 |