Schneider Electric RM22LG11MR level control relay, Harmony Control Relays, 8A, 1CO, 24…240V AC DC
Code: SCHRM22LG11MR
Unit of measure:
EACH
Description
LEVEL CONTROL RELAY RM22-LG - RANGE 5K #
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Relative humidity | 93-97 % at 25-55 °C conforming to IEC 60068-2-30 |
[Us] rated supply voltage | 24...240 V AC/DC 50/60 Hz- non self-powered |
Dielectric test voltage | 2.5 kV- 1 min AC 50 Hz conforming to IEC 60255-27 |
Time delay type | without |
Safety reliability data | MTTFd = 125.5 years |
Maximum switching voltage | 250 V AC |
Electromagnetic compatibility | surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5 |
Maximum electrode voltage | 12 V AC |
Minimum switching current | 10 mA at 5 V DC |
Cable capacitance | 2.2 nF at St (Standard Sensitivity) for probe cable |
Supplier Code | RM22LG11MR |
Ambient air temperature for storage | -40-70 °C |
Supply voltage limits | 20.4-264 V AC/DC |
Vibration resistance | 1 gn (f= 10-58.1 Hz) not in operation conforming to IEC 60068-2-6 |
Sensitivity scale | 5...100 kOhm St (Standard Sensitivity) |
Repeat accuracy | +/- 2 % for time delay |
Insulation | between supply and measurement |
Shock resistance | 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27 |
Contacts type and composition | 2 C/O |
Control type | with test button |
IP degree of protection | IP50 (front panel) conforming to IEC 60529 |
Range | Harmony Control Relays |
Overvoltage category | III conforming to IEC 60664-1 |
Measurement range | 5...100 kOhm |
Electrical durability | 100000 cycles |
Functionality | resistive probe detection |
Mounting position | any position |
Pollution degree | 3 conforming to IEC 60664-1 |
Tightening torque | 0.6-1 N.m conforming to IEC 60947-1 |
Maximum supply current for sensors | 1 mA |
Relay type | level control relay |
Connections - terminals | screw terminals- 1 x 0.5...1 x 3.3mm² (AWG 20...AWG 12) solid without cable end |
Output contacts | 2 C/O |
Maximum cable distance between devices | 1000 m between probe and delay |
[In] rated current | 8 A |
Mounting support | 35mm DIN rail conforming to IEC 60715 |
Mechanical durability | 10000000 cycles |
Relay monitored parameters | detection by resistive probes |
Maximum switching current | 8 A AC |
Switching capacity in VA | 2000 VA |
Housing material | self-extinguishing plastic |
Width | 22.5mm |
Measurement error | 0.05 %/°C with temperature variation |
Nominal output current | 8 A |
[Uc] control circuit voltage | 24...240 V |
Compatibility code | RM22 |
Maximum electrode current | 1 mA |
Sensitivity adjustment | 5-100 % |
Contacts material | cadmium free |
Relay name | RM22L |
Standards | IEC 60255-1 |
Brand Name | Schneider Electric |
Product certifications | CCC |
Immunity to microbreaks | 90 ms AC |
Utilisation category | AC-1 conforming to IEC 60947-4-1 |
Maximum power consumption in W | 1.5 W DC |
Net weight | 0.1 kg |
Product or component type | level control relay |
Run-up delay at power-up | 0.6 s |
Have questions about this product?
Do you need more information? We are here to help. Click below to contact us now!
Get in touchWe would love your opinion
Was the information on this page helpful?