Schneider Electric ATSU01N222LT Soft starter for asynchronous motor, Altistart 01, ATSU01, 22 A-200..480 V-4..11 KW
Code: SCHATSU01N222LT
Unit of measure:
EACH
Description
SOFT-START STOP 22A 200 480V
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Product destination | asynchronous motors |
Relative humidity | 5-95 % without condensation or dripping water conforming to EN/IEC 60068-2-3 |
[Us] rated supply voltage | 200...480 V - 10...10 % |
Discrete input voltage | 24...40 V |
Operating position | vertical +/- 10 degree |
Maximum switching voltage | 440 V relay outputs |
Electromagnetic compatibility | damped oscillating waves level 3 conforming to IEC 61000-4-12 |
Deceleration time symb | adjustable from 1 to 10 s |
Ambient air temperature for operation | 40-50 °C (with current derating of 2 % per °C) |
Minimum switching current | 10 mA at 6 V DC for relay outputs |
Electrical connection | 4mm screw clamp terminal - flexible without cable end 2 1.5...6mm² AWG 10 power circuit |
Discrete output voltage | 24 V (voltage limits: 6...30 V) open collector logic |
Current consumption | 100 mA |
Motor starter type | soft starter |
Output voltage | <= power supply voltage |
Supplier Code | ATSU01N222LT |
Supply voltage limits | 180-528 V |
Ambient air temperature for storage | -25-70 °C conforming to EN/IEC 60947-4-2 |
Discrete output type | relay outputs R1A- R1C NO |
Network frequency | 47.5...63 Hz |
Power dissipation in W | 222.5 W in transient state |
Vibration resistance | 1.5mm peak to peak (f= 3-13 Hz) conforming to EN/IEC 60068-2-6 |
Network number of phases | 3 phases |
Function available | integrated bypass |
Shock resistance | 15 gn for 11 ms conforming to EN/IEC 60068-2-27 |
Motor power kW | 5.5 kW- 3 phases at 230 V |
IP degree of protection | IP20 |
Range | Altistart U01 and TeSys U |
Assembly style | with heat sink |
Tightening torque | 0.5-0.5 N.m |
Pollution degree | 2 conforming to EN/IEC 60947-4-2 |
Input output isolation | galvanic between power and control |
Power range | 7-11 kW at 380-440 V 3 phases |
Product specific application | simple machine |
IcL starter rating | 22 A |
Discrete input logic | positive LI1- LI2- BOOST at State 0: < 5 V and <= 0.2 mA at State 1: > 13 V- >= 0.5 mA |
Depth | 170mm |
Starting time | adjustable from 1 to 10 s |
Type of start | start with voltage ramp |
Maximum switching current | relay outputs: 2 A at 250 V AC AC-15 cos phi = 0.5 and L/R = 20 ms inductive load |
Height | 314mm |
Width | 45mm |
Operating altitude | > 1000 m with current derating of 2.2 % per additional 100 m |
Display type | 1 LED (green) for starter powered up |
[Uc] control circuit voltage | 24 V DC +/- 10 % |
Device short name | ATSU01 |
Marking | CE |
Standards | EN/IEC 60947-4-2 |
Product certifications | CCC |
Brand Name | Schneider Electric |
Discrete output current | 3 A AC-15 |
Supply frequency | 50...60 Hz - 5...5 % |
Motor power hp | 10 hp- 3 phases at 460 V |
Utilisation category | AC-53B conforming to EN/IEC 60947-4-2 |
Discrete input type | logic (LI1- LI2- BOOST) stop- run and boost on start-up functions <= 8 mA 27 kOhm |
Net weight | 0.49 kg |
Starting torque | 30...80 % of starting torque of motor connected directly on the line supply |
Product or component type | soft starter |
We would love your opinion
Was the information on this page helpful?
Thanks for your feedback!
Can't find what you're looking for?
Request now
We can source just about anything, submit a request and we'll get back to you soon.