Schneider Electric ATS480C14Y Soft starter, Altistart 480, 140A, 208 to 690V AC, control supply 110 to 230V AC
Code: SCHATS480C14Y
Unit of measure:
EACH
Description
SOFT STARTER ATS480 140A 208 TO 690V
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Product destination | asynchronous motors |
With safety function Safe brake management (SBC/SBT) | false |
Relative humidity | 0-95 % without condensation or dripping water conforming to IEC 60068-2-3 |
Data format | 8 bits- configurable odd- even or no parity |
With safety function Safe Speed Monitor (SSM) | false |
Maximum deflection under vibratory load (during operation) | 1.5mm at 2...13 Hz |
Ambient air temperature for operation | -15-40 °C (without derating) |
Connector type | 1 RJ45 |
Minimum switching current | 100 mA at 12 V DC for relay outputs |
Analogue output type | current output AQ1: 0...20 mA or 0...10 V- impedance <500 Ohm |
Ambient air temperature for storage | -25-70 °C |
Number of addresses | 0-227 for Modbus serial |
Discrete output type | (DQ2) programmable digital output <= 30 V |
Apparent power | 0.09 kVA |
Discrete input number | 4 |
Protection type | line supply phase loss: motor |
Motor power kW | 30.0 kW at 230 V in the motor supply line heavy duty |
Device connection | to the motor delta terminals |
With safety function Safely Limited Position (SLP) | false |
Option card | communication module for CANopen Sub-D |
Pollution degree | level 3 |
With sft fct Safe Stop 2 (SS2) | false |
With safety function Safely Limited Speed (SLS) | false |
Product specific application | process and infrastructures |
Input compatibility | DI3: discrete input level 1 PLC conforming to IEC 61131-2 |
Accuracy class | class 10E |
Discrete input logic | programmable digital input at State 0: < 5 V |
With safety function Safe torque off (STO) | false |
Depth | 272.0mm |
Volume of cooling air | 138.0 m3/h |
Output current drift | 150-700 % |
Maximum deflection under vibratory load (during transport) | 1.75mm at 2...9 Hz |
Width | 200.0mm |
Operating altitude | > 1000...4000 m with current derating 1 % per 100 m |
Device short name | ATS480 |
Maximum acceleration under vibratory load (during storage) | 10 m/s² at 9...200 Hz |
Power loss static current independent | 25.0 W |
Method of access | slave Modbus serial |
Output compatibility | open collector level 1 PLC conforming to IEC 65A-68 |
Relay output number | 3 |
Analogue output number | 1 |
[Ui] rated insulation voltage | 690 V |
Transmission frame | RTU |
Analogue input number | 1 |
Supply frequency | 50...60 Hz - 20...20 % |
Environmental class (during operation) | class 3S2 according to IEC 60721-3-3 |
Torque control | true |
Discrete input type | (DI4) programmable as logic input- 3500 Ohm |
Net weight | 12.4 kg |
Transmission rate | 1200...256000 bit/s |
[Us] rated supply voltage | 208...690 V - 15...10 % |
With safety function Safe Stop 1 (SS1) | false |
Operating position | vertical +/- 10 degree |
Electromagnetic compatibility | conducted and radiated emissions with bypass level B conforming to IEC 60947-4-2 |
With safety function Safe Direction (SDI) | false |
Noise level | 50.0 dB |
Supplier Code | ATS480C14Y |
Network frequency | 50/60 Hz |
Type of polarization | no impedance for Modbus serial |
Communication data link | serial |
With safety function Safe Operating Stop (SOS) | false |
Network number of phases | 3 phases |
With safety function Safe Position (SP) | false |
Function available | single direction |
Analogue input type | PTC2 PTC/Pt 100 temperature probe |
Maximum acceleration under shock load (during transport) | 100 m/s² at 11 ms |
Communication port protocol | Modbus serial |
IP degree of protection | IP00 |
Range | Altivar Soft Starter ATS480 |
Display screen available | true |
[Ie] rated operational current | normal duty: 140.0 A (at <40 °C) |
Maximum acceleration under vibratory load (during transport) | 10 m/s² at 9...200 Hz |
Power loss per device current dependent | 366.0 W |
Maximum permanent current | 110.0 A at 40 °C for heavy duty |
Suitable for mounting onto standard rails | false |
Maximum switching current | |
Integrated motor overload protection | true |
Height | 340.0mm |
Relay output type | relay outputs R1A 1 NO |
Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 13...200 Hz |
[Uc] control circuit voltage | 110...230 V AC 50/60 Hz - 15...10 % |
Rated current pwr loss specification | 140.0 A |
Discrete output number | 2 |
Marking | UKCA |
Maximum deflection under vibratory load (during storage) | 1.75mm at 2...9 Hz |
Standards | IEC 60664-1 |
Product certifications | RCM |
With safety function Safe programmable logic | false |
Brand Name | Schneider Electric |
Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms |
[Uimp] rated impulse withstand voltage | 6 kV |
Motor power hp | 125.0 hp at 575 V normal duty |
Utilisation category | AC-53A |
Physical interface | 2-wire RS 485 |
Maximum acceleration under shock load (during storage) | 100 m/s² at 11 ms |