Description
Schneider LP1D65008FD TeSys Deca contactor,4P(2NO+2NC),AC-1,<=440V 80A,110V DC coil
TeSys LR9D electronic overload relay, 8A/690V, thermal setting range 1.6-8A, selectable tripping class 5-10-20-30, for protection of 3-phase motors 0.75-3kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, buttons for test, stop and reset as well as manual-automatic reset selector, dipswitches for tripping class selection, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D09-D38. Mounting on DIN rail or screw fixing, separated from contactor, with use of the terminal block LAD7B205 (to be ordered separately). Multi-standards certified (IEC, UL, CSA, CCC), Green Premium compliant (RoHs/Reach).
Features:
⢠Easy for selection
⢠Trip indication
⢠Efficiency maintenance
⢠Class 10 A and 20
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Tripping threshold | 1.25 In conforming to IEC 60947-4-1 |
Mount | Under contactor |
Electromagnetic compatibility | resistance to electrostatic discharge: 8 kV conforming to IEC 61000-4-2 |
Associated fuse rating | 5 A BS for signalling circuit |
Thermal overload class | class 5âĤ30 |
Depth | 79.9mm |
Ambient air temperature for operation | -25-70 °C conforming to IEC 60255-8 |
Mounting support | plate- with specific accessories |
[Ith] conventional free air thermal current | 5 A for signalling circuit |
Voltage | 690 V |
Supplier Code | LR9D08 |
Ambient air temperature for storage | -55-80 °C |
Height | 72.5mm |
Width | 45mm |
Operating altitude | 2000 m without derating |
Power consumption in W | 300 mW |
Dielectric strength | 6 kV 50 Hz conforming to IEC 60255-5 |
Device short name | LR9D |
Phase failure sensitivity | phase difference > 40% 3-3 s conforming to IEC 60947-4-1 |
Time range | 1.5...4 min - automatic reset time |
Product compatibility | LC1D18 |
Mechanical robustness | shocks 11 ms: 15 gn conforming to IEC 60068-2-7 |
[Ue] rated operational voltage | 660 V for signalling circuit |
Control type | white 2 microswitches: adjustable trip class |
[Ui] rated insulation voltage | signalling circuit: 690 V |
IP degree of protection | IP20 front face conforming to IEC 60529 |
Range | TeSys |
Weight | 0.18 kg |
Standards | UL 60947-5-1 |
Product certifications | IECEE CB Scheme |
Brand Name | Schneider Electric |
Item Name | Elctronic OLR |
[Uimp] rated impulse withstand voltage | 6 kV |
IP Rating | IP20 |
Product name | TeSys LRD |
Relay application | motor protection |
Tightening torque | power circuit: 3.1 N.m on screw clamp terminals |
Thermal protection adjustment range | 1.6-8 A |
Net weight | 0.18 kg |
Current | 1.6 - 8.0A |
Product or component type | electronic thermal overload relay |
Connections - terminals | power circuit: screw clamp terminals 1 cable 16-16mm² - cable stiffness: solid or flexible - without cable end |