Description
TeSys LRD thermal overload relay, 38A/690V, thermal setting range 30-38A, tripping class 10A, for protection of 3-phase motors 18.5kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D32-D38. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD7B106 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine), Green Premium compliant (RoHs/Reach).
Features:
• Free of Substances of Very High Concern above the threshold
•
•
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Mount | Plate, with specific accessories |
Thermal overload class | class 10A conforming to IEC 60947-4-1 |
Ambient air temperature for operation | -20-60 °C without derating conforming to IEC 60947-4-1 |
Current Type | AC |
Supplier ref | LRD35 |
Contactor | LC1D32, LC1D38 |
[Ith] conventional free air thermal current | 5 A for signalling circuit |
Supplier Code | LRD35 |
Ambient air temperature for storage | -60-70 °C |
Trip Class | Class 10A |
GrosWeight | 140.000 g |
Permissible current | 0.1 A at 250 V DC-13 for signalling circuit |
Network frequency | 0...400 Hz |
Dielectric strength | 1.89 kV at 50 Hz conforming to IEC 60947-1 |
Warranty | 18 months |
Network type | AC |
Terminal Type | Screw Clamp |
Control type | blue push-button: reset |
IP degree of protection | IP20 conforming to IEC 60529 |
Range | TeSys Deca |
Flame retardance | V1 conforming to UL 94 |
Weight | 0.124 kg |
Frequency Rating | 0 - 400 Hz |
Item Name | Overload Relay |
Volume | 343.980 cm3 |
Tightening torque | power circuit: 2.5 N.m - on screw clamp terminals |
Thermal protection adjustment range | 30-38 A |
Auxiliary contact composition | 1 NO + 1 NC |
Current | 30 - 38A |
Connections - terminals | power circuit: screw clamp terminals 1 cable(s) 1-6mm² flexible with cable end |
Tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
Associated fuse rating | 4 A BS for signalling circuit |
Standard | CSA, UL Listed |
Depth | 70mm |
Mounting support | rail- with specific accessories |
Climatic withstand | conforming to IACS E10 |
Voltage | 690 V |
Degree of Protection | IP20 |
Height | 66mm |
Width | 45mm |
Temperature Rating | -20 to 60 deg C |
Device short name | LRD |
Phase failure sensitivity | tripping current 130 % of Ir on two phase- the last one at 0 |
Compatibility code | LRD |
Product compatibility | LC1D38 |
Mechanical robustness | shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7 |
[Ue] rated operational voltage | 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
[Ui] rated insulation voltage | power circuit: 600 V conforming to UL |
Temperature compensation | -20-60 °C |
Standards | CSA C22.2 No 60947-4-1 |
Product certifications | ATEX INERIS |
Brand Name | Schneider Electric |
EAN/UPC | 3389110346862 |
[Uimp] rated impulse withstand voltage | 6 kV |
Type | Thermal |
Reset Type | Manual/Automatic |
IP Rating | IP20 |
Length | 4.900 cm |
Product name | TeSys Deca |
Relay application | motor protection |
Frequency | 0...400 Hz |
Net weight | 0.124 kg |
Product or component type | differential thermal overload relay |
We would love your opinion
Was the information on this page helpful?
Thanks for your feedback!
We can source just about anything, submit a request and we'll get back to you soon.