THERMAL OVERLOAD RELAY 37-50A D40A-D80A
THERMAL OVERLOAD RELAY 37-50A D40A-D80A
image/svg+xml
Schneider LRD350 TeSys, TeSys Deca, Thermal overload relay, 690VAC, 37 to 50A, 1NO+1NC, class 10A, EverLink BTR screw

Select products - now easier than ever

Discover our Product Selector tool to easily choose the products you need, in just a few clicks.

Launch Product selector Learn more
Show More

Schneider LC1D50ABBE TeSys, TeSys Deca, Contactor, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 50A, 24VDC coil, EverLink

TeSys LRD thermal overload relay, 50A/690V, thermal setting range 37-50A, tripping class 10A, for protection of 3-phase motors 22kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by EverLink BTR screw terminals , it connects directly to the bottom terminals of 3-pole contactors LC1D40A-D80A. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD96560 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHs/Reach).