Description
BENDER B91067010 Insulation monitoring device, Type iso685-D, Nominal system voltage range Un - AC 0…690 V, 0.1…460 Hz, DC 0…1000 V, Supply voltage AC 24…240 V, 50…400 Hz, DC 24…240 V
Insulation monitoring device, Type iso685-D, Nominal system voltage range Un - AC 0…690 V, 0.1…460 Hz , DC 0…1000 V , Supply voltage Us - AC 24…240 V, 50…400 Hz , DC 24…240 V , c/w a high-resolution graphic LC Integrated display and control elements for direct operating of the device functions.DIN Mount ,Article # B91067010
Features:
• The device version iso685-D features a high-resolution graphic LC display and control elements for direct operating of the device functions.
• Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)
• ISOMETER® for IT AC systems with galvanically connected rectifiers or inverters and for IT DC systems (IT = unearthed systems)
• Two separately adjustable response value ranges of 1 kΩ…10 MΩ
• Current or voltage output 0(4)…20 mA, 0…400 μA, 0…10 V, 2…10 V (galvanically separated), which is analogous to the measured insulation value of the system
• RS-485/BS (Bender sensor bus) for data exchange with other Bender devices
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Brand Name | Bender |
Mounting | DIN Mount |
Category | Monitoring & Measurement |
Function Type | Insulation monitoring device |
Length | 108mm |
Voltage | Nominal system voltage range Un - AC 0…690 V |
Height | 93mm |
Range | Type iso685-D |
Width | 110mm |
Weight | 390g |