Description
Honeywell FC-TELD-0001 Earth Leakage Detector terminal (TELD), Analog Input voltage 24VDC, Analog Input Current 10mA (No Earth Fault Present). Din Mounted
Earth Leakage Detector terminal (TELD), Analog Input voltage 24VDC, Analog Input Current 10mA (No Earth Fault Present), Earth Voltage typically +4.1VDC, Resistor approximately 2.8kOhm, Earth Fault Detection Threshold approximately 0.6mA flowing into FC-TELD-0001 and approximately 0.2mA flowing ifrom FC-TELD-0001., Din Mounted
Features:
• The TELD-0001 is an Earth Fault Monitor in a terminal shaped housing. It is used to detect earth faults in all circuits and wiring that are galvanically connected in a power supply group.
• The TELD-0001 brings earth voltage to (approximately) +4Vdc as referenced to the 0Vdc of the monitored power supply group.
• The (0-20mA) current that is drawn by the TELD-0001 gives the control system an indication of the type of earth fault present.
• The Earth Leak Detection (TELD) should be placed near the connected IOTA channel (Example: On a piece of DIN rail at the side). The TELD can be operated in an ambient air temperature range of -40°C to +75°C. Connect the TELD earth wire and the instrument earth bar with a short wire. Route the earth wire two times through ferrite
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
| Brand Name | Honeywell |
| Mounting | Din Mounted |
| Category | Monitoring & Measurement |
| Function Type | Earth Leakage Detector |
| Length | 80mm |
| Voltage | Analog Input Voltage 24 VDC +30/-15% (with approximately 250 Ohm series impedance) |
| Height | 70mm |
| Width | 20mm |