Schneider Electric LC1E1810B5 Contactor,Easy TeSys Control,LC1E,3P(3NO),AC-3,<=440V,18A,24V AC coil,50Hz,1NO auxiliary contact
Code: SCHLC1E1810B5
Unit of measure:
EACH
Description
3P CONTACTOR TESYS E 1NO 7 5KW 400V AC3
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Contactor application | resistive load |
Maximum operating rate | 1800 cyc/h 60 °C |
Non-overlap time | 1.5 ms on de-energisation guaranteed between NC and NO contact |
Minimum switching current | 5 mA for control circuit |
Irms rated making capacity | 180 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
[Ith] conventional free air thermal current | 32 A (at 55 °C) for power circuit |
Supplier Code | LC1E1810B5 |
[Icw] rated short-time withstand current | 40 A 40 °C - 600 s for power circuit |
Inrush power in VA | 95-95 VA 60 Hz cos phi 0.75 (at 20 °C) |
Hold-in power consumption in VA | 8.5-8.5 VA 60 Hz cos phi 0.3 (at 20 °C) |
Motor power kW | 7.5 kW at 380...400 V |
Insulation resistance | > 10 MOhm for control circuit |
IP degree of protection | IP2X conforming to IEC 60529 |
Range | Easy TeSys |
Overvoltage category | III |
Electrical durability | 1200000 cycles AC-3 |
Protective treatment | TH (pollution degree 3) conforming to IEC 60068-2-30 test Db |
Pollution degree | 3 |
Tightening torque | control circuit: 1.2 N.m |
Average impedance | 2.5 mOhm - Ith 32 A 50 Hz for power circuit |
Auxiliary contact composition | 1 NO |
[Ie] rated operational current | 32 A (at <55 °C) at <= 440 V AC AC-1 for power circuit |
Connections - terminals | control circuit: screw clamp terminals 2 1-2.5mm² - cable stiffness: flexible with cable end |
Control circuit type | AC at 50 Hz |
Associated fuse rating | 35 A gG at <= 690 V coordination type 1 for power circuit |
Depth | 80mm |
Mounting support | plate |
Pole contact composition | 3 NO |
Fire resistance | 850 °C conforming to IEC 60695-2-1 |
Mechanical durability | 10000000 cycles |
Permissible ambient air temperature around the device | -5-55 °C operation |
Minimum switching voltage | 17 V for control circuit |
Height | 74mm |
Poles description | 3P |
Width | 45mm |
Operating altitude | 3000 m without derating |
Operating time | 4...19 ms on opening |
Device short name | LC1E |
[Uc] control circuit voltage | 24 V AC 50 Hz |
Mechanical robustness | shocks contactor closed (10 Gn for 11 ms) |
[Ue] rated operational voltage | power circuit: <= 690 V AC 50/60 Hz |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
Standards | IEC 60947-4-1 |
Control circuit voltage limits | 0.3...0.6 Uc (-5-55 °C):drop-out 50 Hz |
Product certifications | CE |
Brand Name | Schneider Electric |
Heat dissipation | 2-3 W for control circuit |
[Uimp] rated impulse withstand voltage | 6 kV coil not connected to the power circuit conforming to IEC 60947 |
Power dissipation per pole | 2.6 W AC-1 |
Rated breaking capacity | 144 A at 440 V for power circuit conforming to IEC 60947 |
Utilisation category | AC-3e |
Net weight | 0.3 kg |
Product or component type | contactor |